一、用途
适用于交流额定电压10kV及以下架空电力电缆线路
二、型号及名称
型号 | 名称 | 名称 |
JKLGYJ | 钢铝绞线芯交联聚乙烯绝缘架空电缆 | 架空固定敷设用电缆架设时,应考虑电缆和树木保持一定距离,电缆运行时,允许电缆和树木频繁接触 |
JKLGYJ/Q | 钢铝绞线芯交联聚乙烯薄绝缘架空电缆 | 架空固定敷设用电缆架设时,应考虑电缆和树木保持一定距离,电缆运行时,只允许电缆和树木作短时接触 |
三、规格
型号 | 额定电压kV | 芯数 | 标称截面mm2 | |
铜芯 | 铝芯 | |||
JKLGYJ、JKLGYJ/Q | 10及以下 | 1 | 25~300 | 4~70 |
四、性能参数
1、导体结构、直流电阻及拉断力
标称截面铝/钢 | 结构根数直径mm | 导体外径mm | 20℃导体直流电阻Ω/km | 导体拉断力不小于N | |
铝 | 钢 | ||||
25/4 | 6/2.32 | 1/2.32 | 6.96 | 1.131 | 9290 |
35/6 | 6/2.72 | 1/2.70 | 8.16 | 0.8230 | 12630 |
50/8 | 6/3.20 | 1/3.20 | 9.60 | 0.5946 | 16870 |
50/30 | 12/2.32 | 7/2.32 | 11.60 | 0.5692 | 42620 |
70/10 | 6/3.80 | 1/3.80 | 11.40 | 0.4217 | 23390 |
70/40 | 12/2.72 | 7/2.72 | 13.60 | 0.4141 | 58300 |
95/15 | 26/2.15 | 7/1.67 | 13.61 | 0.3058 | 35000 |
95/20 | 7/4.16 | 7/1.85 | 13.87 | 0.3019 | 37200 |
95/55 | 12/3.20 | 7/3.20 | 16.00 | 0.2992 | 78110 |
120/7 | 18/2.90 | 1/2.90 | 14.50 | 0.2422 | 27570 |
120/20 | 26/2.38 | 7/1.85 | 15.07 | 0.2496 | 41000 |
120/25 | 7/4.72 | 7/2.10 | 15.74 | 0.2345 | 47888 |
120/70 | 12/3.60 | 7/3.60 | 18.00 | 0.2364 | 98370 |
150/8 | 18/3.20 | 1/3.20 | 16.00 | 0.1989 | 32860 |
150/20 | 24/2.78 | 7/1.85 | 16.67 | 0.1980 | 46630 |
150/25 | 26/2.70 | 7/2.10 | 17.10 | 0.1939 | 54110 |
150/35 | 30/3.50 | 7/2.50 | 17.50 | 0.1962 | 65020 |
185/10 | 18/3.60 | 1/3.60 | 18.00 | 0.1572 | 40880 |
185/25 | 24/3.15 | 7/2.10 | 18.90 | 0.1542 | 59420 |
185/30 | 26/2.98 | 7/2.32 | 18.88 | 0.1592 | 64320 |
185/45 | 30/2.80 | 7/2.80 | 19.60 | 0.1564 | 80190 |
210/10 | 18/3.80 | 1/3.80 | 19.00 | 0.1411 | 45140 |
210/25 | 24/3.33 | 7/2.22 | 19.98 | 0.1380 | 65990 |
210/35 | 26/3.22 | 7/2.50 | 20.38 | 0.1363 | 74250 |
210/50 | 30/2.98 | 7/2.98 | 20.86 | 0.1381 | 90830 |
240/30 | 24/3.60 | 7/2.40 | 21.60 | 0.1181 | 75620 |
240/40 | 26/3.42 | 7/2.62 | 21.66 | 0.1209 | 83370 |
240/50 | 30/3.20 | 7/3.20 | 22.40 | 0.1198 | 102100 |
300/15 | 42/3.00 | 7/1.67 | 23.01 | 0.09724 | 68060 |
300/20 | 45/2.93 | 7/1.95 | 23.43 | 0.09520 | 75680 |
300/25 | 48/2.85 | 7/2.22 | 23.76 | 0.09433 | 83410 |
300/40 | 24/3.99 | 7/2.66 | 23.94 | 0.09614 | 92220 |
300/50 | 26/3.8 | 7/2.98 | 24.26 | 0.09636 | 103400 |
300/70 | 30/3.60 | 7/3.60 | 25.20 | 0.09463 | 128000 |
2、电缆经受1min试验电压,不击穿
额定电压UKV | 1 | 10 | |
试验电压USKV | 3.5 | 普通绝缘结构电缆 | 轻型薄绝缘结构电缆 |
18 | 12 |
3、绝缘电阻:室温下,将电缆浸于水中1h,施加80~500V直流电压,稳定时间为1min~5min,额定电压10kV电缆的绝缘电阻不小于1500MΩ·km,轻型薄绝缘结构电缆的绝缘电阻不小于1000 MΩ·km
五、使用特性
1、额定电压1kV、10kV
2、电缆的敷设温度不低于0℃
3、电缆导体的长期允许工作温度为90℃
4、电缆的弯曲半径:1kV架空电缆不小于电缆外径的6倍,10kV架空电缆不小于电缆外径的20倍